H3YN-B

Features

Kompakte Multifunktions-Zeitrelais mit Stecksockel

  • Für eine einfache Verdrahtung ist der Stecksockel mit Push-in-Plus-Technologie erhältlich: PYF-__-PU
  • Ermöglicht einfachen Austausch und spart Zeit bei der Wartung
  • Platz sparend durch schlankes Design mit 21,5 mm Breite
  • Großer, transparenter Zeiteinstellring erleichtert die Zeiteinstellung
Spezifikationen & Bestellinfo

Ordering information

Operating modes

Control output

Supply voltage

Order code

Short-time range (0.1 s to 10 min)

Long-time range (0.1 m to 10 h)

On-delay, Interval,
Flicker OFF-start, Flicker ON Start

DPDT

24 VAC

H3YN-2-B AC24

H3YN-21-B AC24

24 VDC

H3YN-2-B DC24

H3YN-21-B DC24

12 VDC

H3YN-2-B DC12

H3YN-21-B DC12

100 to 120 VAC

H3YN-2-B AC100-120

H3YN-21-B AC100-120

200 to 230 VAC

H3YN-2-B AC200-230

H3YN-21-B AC200-230

4PDT

24 VAC

H3YN-4-B AC24

H3YN-41-B AC24

24 VDC

H3YN-4-B DC24

H3YN-41-B DC24

12 VDC

H3YN-4-B DC12

H3YN-41-B DC12

100 to 120 VAC

H3YN-4-B AC100-120

H3YN-41-B AC100-120

200 to 230 VAC

H3YN-4-B AC200-230

H3YN-41-B AC200-230

4PDT, Twin Contact

24 VDC

H3YN-4-Z-B DC24

H3YN-41-Z-B DC24

Accessories

Plug-in Socket

Type

Timer

Order code

Screwless socket with Push-in plus technology

H3YN-2-B/H3YN-21-B

PYF-08-PU-L

H3YN-4-B/H3YN-41-B/
H3YN-41-Z-B

PYF-14-PU-L

Hold-down clip

Type

Order code

PYF-08-PU-L/PYF-14-PU-L

Y92H-3 (2 pcs in a pack)

Specifications

Item

H3YN-2-B/H3YN-21-B

H3YN-4-B/H3YN-41-B/H3YN-41-Z-B

Time ranges

0.1 s to 10 min (1 s, 10 s, 1 min, or 10 min max. selectable)

0.1 min to 10 h (1 min, 10 min, 1 h, or 10 h max. selectable)

Rated supply voltage1

24, 100 to 120, 200 to 230 VAC (50/60 Hz), 12, 24 VDC

Pin type

Plug-in

Operating mode

ON-delay, interval, flicker OFF-start, or flicker-ON start selectable by DIP switch

Operating voltage range

85% to 110% of rated supply voltage (12 VDC: 90% to 110% of rated supply voltage)2

Reset voltage

10% max. of rated supply voltage

Control outputs

DPDT:
5 A at 250 VAC, resistive load (cos φ = 1)
The minimum applicable load is 1 mA at 5 VDC (P reference value).
Contact materials: Ag

4PDT:
3 A at 250 VAC, resistive load (cos φ = 1)
H3YN-4-B/-41-B series: The minimum applicable load is 1 mA at 1 VDC (P reference value)
H3YN-4-Z/-41-Z-B series: The minimum applicable load is 1 mA at 1 VDC (P reference value)
Contact materials: Au-clad + Ag-alloy

Accuracy of operating time

±1% FS max. (1 s range: ±1%±10 ms max.)

Setting error

±10% ±50 ms FS max.

Reset time

Min. power-opening time: 0.1 s max. (including halfway reset)

Influence of voltage

±2% FS max.

Influence of temperature

±2% FS max.

Ambient temperature

Operating: −10°C to 55°C (with no icing)
Storage: −25°C to 65°C (with no icing)

Degree of protection

IP40 (Terminal screw sections are excluded.)

Size in mm (H × W × D)

28 × 21.5 × 52.6


1. Refer to Safety Precautions for All Times when combining the timer with an AC 2-wire proximity sensor.
2. When using the H3RN in any place where the ambient temperature is more than 50°C, supply 90% to 110% of the rated voltages (12 VDC: 95% to 110% of the rated voltage).
1. Refer to Safety Precautions for All Times when combining the timer with an AC 2-wire proximity sensor.
2. When using the H3RN in any place where the ambient temperature is more than 50°C, supply 90% to 110% of the rated voltages (12 VDC: 95% to 110% of the rated voltage).

Abonnieren Sie unsere Produkt-Updates

Profitieren Sie von Newslettern über Produktinnovationen, Lösungen und Services.

Vielen Dank für Ihr Interesse an unseren eNews. Sie erhalten umgehend eine Email von uns mit einem Link zur Bestätigung Ihrer Newsletter-Bestellung. Dieses Vorgehen basiert aus unseren rechtlichen Hinweisen.

Es liegen zur Zeit technische Probleme vor. Ihre Übertragung war nicht erfolgreich. Entschuldigen Sie dies bitte und versuchen es später noch einmal. Details

Download

Produktdokumentation

Laden Sie sich Datenblätter, Handbücher und Broschüren herunter.

Durchsuchen Sie unser Download-Center

Schulungskurse

Bei unseren Schulungen profitieren Sie von der Kompetenz unserer besten Ingenieure. Für Anfänger bis Fortgeschrittene geeignet

Sehen Sie sich einen Schulungskurs an.